Capacité nominale kV · A |
Gamme de classification de niveau de combinaison de tension |
Numéro de groupe de connexion |
Perte de charge à vide kW |
Perte de charge kW |
Courant à vide % |
Impédance de court-circuit % |
||
|
Gamme de classification haute tension kV |
Haute tension kV |
Basse tension kV |
||||||
|
30 |
± 2 × 2,5 ± 5 |
6 6.3 10 10.5 |
0.4 |
Dyn11 Yzn11 Yyn0 |
0.065 |
0.455/0.43 |
1.5 |
4 |
|
50 |
0.08 |
0.655/0.625 |
1.3 |
|||||
|
63 |
0.09 |
0.785/0.745 |
1.2 |
|||||
|
80 |
0.105 |
0.945/0.9 |
1.2 |
|||||
|
100 |
0.12 |
1.14/1.08 |
1.1 |
|||||
|
125 |
0.135 |
1.36/1.295 |
1.1 |
|||||
|
160 |
0.16 |
1.665/1.585 |
1 |
|||||
|
200 |
0.19 |
1.97/1.87 |
1 |
|||||
|
250 |
0.23 |
2.3/2.195 |
0.9 |
|||||
|
315 |
0.27 |
2.76/2.63 |
0.9 |
|||||
|
400 |
0.33 |
3.25/3.095 |
0.8 |
|||||
|
500 |
0.385 |
3.9/3.71 |
0.8 |
|||||
|
630 |
Dyn11 Yyn0 |
0.46 |
4.46 |
0.6 |
||||
|
800 |
0.56 |
5.4 |
0.6 |
4.5 |
||||
|
1000 |
0.665 |
7.415 |
0.6 |
|||||
|
1250 |
0.78 |
8.64 |
0.5 |
|||||
|
1600 |
0.94 |
10.44 |
0.5 |
|||||
|
2000 |
1.085 |
13.18 |
0.4 |
5 |
||||
|
2500 |
1.28 |
13.36 |
0.4 |
|||||
|
Remarque 1 : Pour les transformateurs d'une capacité nominale de 500kV · A et moins, la valeur de perte de charge au-dessus de la barre oblique dans le tableau s'applique au groupe de connexion Dynll ou Yznll, et la valeur de perte de charge sous la barre oblique est applicable au groupe de connexion Yyn0. Remarque 2 : Lorsque le taux de charge annuel moyen du transformateur est de 35% à 40%, l'efficacité de fonctionnement maximale peut être obtenue en utilisant la valeur de perte de la table. |
||||||||